ZXBX-12 Portable Electricity Recording Analyzer

ZXBX-12 portable power recording analyzer is a transient signal recording instrument developed for power system applications. The instrument's internal software is preset with a test template for generator debugging, so users can easily complete generator short-circuit characteristics through the recorder, no-load characteristic test, excitation system disturbance test, excitation system 10% step test, deexcitation constant measurement, self-quasi-simultaneous synchronization device verification, unit load rejection record and tests.

This type of power recording analyzer has rich software components so that users can freely perform graphical analysis, combination calculation, effective value calculation, AC power calculation, three-phase symmetry analysis, harmonic analysis, and curve correlation through the software components.

Features
Technical indicators

1. 12-channel low-voltage / current analog quantity acquisition, voltage input range -10V ~ 10V, -200V ~ 200V, -400V ~ 400V, current input range -20mA ~ 20mA, 1 channel analog value -100mV ~ 100mV input channel

2. Voltage channel input range, voltage or current signal type selection, software selection

3. Signal acquisition error: -400V ~ 400V error <0.5V

-200V ~ 200V error <0.2V

-10V ~ 10V error <0.01V

-20mA ~ 20mA Error <0.02mA

-100mV ~ 100mV error <0.2mV

4. 12-channel active node switch measurement channel, switch signal range DC12-220V

5. 3-channel switch output channel, the maximum breaking capacity of the switch is AC220V / 1A

6. Split chassis structure, operation terminal allows users to control test and analyze data more conveniently

7. 2 USB ports for data download or keyboard / mouse input

8. 12.1-inch large color screen display, touch screen way to realize human-computer interaction

9. The instrument comes with 8G data storage space

10. Sampling channel input impedance

-10V ~ 10V voltage range input impedance 820k ohm

-200V ~ 200V voltage range Input impedance 820K Euro

-400V ~ 400V voltage range Input impedance 820K Euro

-20mA ~ 20mA current gear input impedance 50 ohm

-100mV ~ 100mV voltage range input impedance> 10M